Response of concrete cast in permeable moulds to severe heating

Oliver Richards, Ieuan Rickard, John Orr, Luke Bisby

Research output: Contribution to journalArticle

2 Citations (Scopus)

Abstract

This paper evaluates the effect that a permeable mould, such as would be used to create fabric-formed concrete, may have on the heat-induced explosive spalling performance of cast concrete, using a novel experimental fire testing method and supported by scanning electron microscopy. Recent research suggests that a concrete cast using fabric formwork will gain durability enhancements at the cast surface that may negatively affect pore-pressure expulsion during severe heating. Six concrete samples were cast using high strength concrete including silica fume and tested using the University of Edinburgh's Heat-Transfer Rate Inducing System (H-TRIS), receiving thermal loading on one surface. Three samples were cast in permeable moulds, formed using a Huesker HaTe PES 70/70 single layer woven geotextile with a characteristic opening size (O90) of 0.1 × 10−3 m. Three samples were cast in conventional impermeable timber moulds. The tests showed no conclusive evidence of differences in thermal profile or differential thermal deflections between the two casting methods; no occurrences of heat-induced explosive spalling were observed for either casting method. However, scanning electron microscopy undertaken on additional samples showed that the test face of samples cast in permeable moulds were over four times less porous compared to their impermeably cast equivalents. This could increase the risk of spalling of samples, particularly in cases where pore-pressure spalling dominates the material response. However, additional fire testing using H-TRIS is needed under a range of heating and loading conditions, before definitive conclusions on the spalling propensity of fabric-formed concrete can be made.

LanguageEnglish
Pages526-538
Number of pages13
JournalConstruction and Building Materials
Volume160
Early online date23 Nov 2017
DOIs
StatusPublished - 30 Jan 2018

Fingerprint

Spalling
Concretes
Heating
Flammability testing
Pore pressure
Casting
Heat transfer
Scanning electron microscopy
Silica fume
Geotextiles
Timber
Durability
Hot Temperature

Keywords

  • Concrete
  • Heating
  • Permeable formwork

ASJC Scopus subject areas

  • Civil and Structural Engineering
  • Building and Construction
  • Materials Science(all)

Cite this

Response of concrete cast in permeable moulds to severe heating. / Richards, Oliver; Rickard, Ieuan; Orr, John; Bisby, Luke.

In: Construction and Building Materials, Vol. 160, 30.01.2018, p. 526-538.

Research output: Contribution to journalArticle

Richards, Oliver ; Rickard, Ieuan ; Orr, John ; Bisby, Luke. / Response of concrete cast in permeable moulds to severe heating. In: Construction and Building Materials. 2018 ; Vol. 160. pp. 526-538.
@article{aaa5835ff7044a56b2c223bf177b9016,
title = "Response of concrete cast in permeable moulds to severe heating",
abstract = "This paper evaluates the effect that a permeable mould, such as would be used to create fabric-formed concrete, may have on the heat-induced explosive spalling performance of cast concrete, using a novel experimental fire testing method and supported by scanning electron microscopy. Recent research suggests that a concrete cast using fabric formwork will gain durability enhancements at the cast surface that may negatively affect pore-pressure expulsion during severe heating. Six concrete samples were cast using high strength concrete including silica fume and tested using the University of Edinburgh's Heat-Transfer Rate Inducing System (H-TRIS), receiving thermal loading on one surface. Three samples were cast in permeable moulds, formed using a Huesker HaTe PES 70/70 single layer woven geotextile with a characteristic opening size (O90) of 0.1 × 10−3 m. Three samples were cast in conventional impermeable timber moulds. The tests showed no conclusive evidence of differences in thermal profile or differential thermal deflections between the two casting methods; no occurrences of heat-induced explosive spalling were observed for either casting method. However, scanning electron microscopy undertaken on additional samples showed that the test face of samples cast in permeable moulds were over four times less porous compared to their impermeably cast equivalents. This could increase the risk of spalling of samples, particularly in cases where pore-pressure spalling dominates the material response. However, additional fire testing using H-TRIS is needed under a range of heating and loading conditions, before definitive conclusions on the spalling propensity of fabric-formed concrete can be made.",
keywords = "Concrete, Heating, Permeable formwork",
author = "Oliver Richards and Ieuan Rickard and John Orr and Luke Bisby",
year = "2018",
month = "1",
day = "30",
doi = "10.1016/j.conbuildmat.2017.11.097",
language = "English",
volume = "160",
pages = "526--538",
journal = "Construction and Building Materials",
issn = "0950-0618",
publisher = "Elsevier",

}

TY - JOUR

T1 - Response of concrete cast in permeable moulds to severe heating

AU - Richards, Oliver

AU - Rickard, Ieuan

AU - Orr, John

AU - Bisby, Luke

PY - 2018/1/30

Y1 - 2018/1/30

N2 - This paper evaluates the effect that a permeable mould, such as would be used to create fabric-formed concrete, may have on the heat-induced explosive spalling performance of cast concrete, using a novel experimental fire testing method and supported by scanning electron microscopy. Recent research suggests that a concrete cast using fabric formwork will gain durability enhancements at the cast surface that may negatively affect pore-pressure expulsion during severe heating. Six concrete samples were cast using high strength concrete including silica fume and tested using the University of Edinburgh's Heat-Transfer Rate Inducing System (H-TRIS), receiving thermal loading on one surface. Three samples were cast in permeable moulds, formed using a Huesker HaTe PES 70/70 single layer woven geotextile with a characteristic opening size (O90) of 0.1 × 10−3 m. Three samples were cast in conventional impermeable timber moulds. The tests showed no conclusive evidence of differences in thermal profile or differential thermal deflections between the two casting methods; no occurrences of heat-induced explosive spalling were observed for either casting method. However, scanning electron microscopy undertaken on additional samples showed that the test face of samples cast in permeable moulds were over four times less porous compared to their impermeably cast equivalents. This could increase the risk of spalling of samples, particularly in cases where pore-pressure spalling dominates the material response. However, additional fire testing using H-TRIS is needed under a range of heating and loading conditions, before definitive conclusions on the spalling propensity of fabric-formed concrete can be made.

AB - This paper evaluates the effect that a permeable mould, such as would be used to create fabric-formed concrete, may have on the heat-induced explosive spalling performance of cast concrete, using a novel experimental fire testing method and supported by scanning electron microscopy. Recent research suggests that a concrete cast using fabric formwork will gain durability enhancements at the cast surface that may negatively affect pore-pressure expulsion during severe heating. Six concrete samples were cast using high strength concrete including silica fume and tested using the University of Edinburgh's Heat-Transfer Rate Inducing System (H-TRIS), receiving thermal loading on one surface. Three samples were cast in permeable moulds, formed using a Huesker HaTe PES 70/70 single layer woven geotextile with a characteristic opening size (O90) of 0.1 × 10−3 m. Three samples were cast in conventional impermeable timber moulds. The tests showed no conclusive evidence of differences in thermal profile or differential thermal deflections between the two casting methods; no occurrences of heat-induced explosive spalling were observed for either casting method. However, scanning electron microscopy undertaken on additional samples showed that the test face of samples cast in permeable moulds were over four times less porous compared to their impermeably cast equivalents. This could increase the risk of spalling of samples, particularly in cases where pore-pressure spalling dominates the material response. However, additional fire testing using H-TRIS is needed under a range of heating and loading conditions, before definitive conclusions on the spalling propensity of fabric-formed concrete can be made.

KW - Concrete

KW - Heating

KW - Permeable formwork

UR - http://www.scopus.com/inward/record.url?scp=85034962735&partnerID=8YFLogxK

U2 - 10.1016/j.conbuildmat.2017.11.097

DO - 10.1016/j.conbuildmat.2017.11.097

M3 - Article

VL - 160

SP - 526

EP - 538

JO - Construction and Building Materials

T2 - Construction and Building Materials

JF - Construction and Building Materials

SN - 0950-0618

ER -