High frequency protection scheme for multi-terminal HVDC overhead lines

S.P. Le Blond, Q. Deng, M. Burgin

Research output: Contribution to conferencePaper

4 Citations (SciVal)
236 Downloads (Pure)

Abstract

This paper proposes a novel protective relaying technique for multi-terminal HVDC system based on the high frequency components in the current signals received at each end of the DC transmission line. A simple model of a mono-pole, ground return, MTDC system is built in ATP draw using a distributed parameter, frequency dependent overhead line model. For this system, the high frequency content in the current signal directly following a fault (at approximately 0.2 kHz) is shown to vary significantly with fault location but not fault resistance. The protection algorithm is then validated in real time using an RTDS system, where both the ATP primary system model and the MATLAB developed algorithm are demonstrated in a real time context.
Original languageEnglish
Number of pages5
Publication statusPublished - Apr 2014
Event12th IET International Conference on Developments in Power System Protection, DPSP 2014; Copenhagen - Copenhagen , Denmark
Duration: 31 Mar 20143 Apr 2014

Conference

Conference12th IET International Conference on Developments in Power System Protection, DPSP 2014; Copenhagen
Country/TerritoryDenmark
CityCopenhagen
Period31/03/143/04/14

Fingerprint

Dive into the research topics of 'High frequency protection scheme for multi-terminal HVDC overhead lines'. Together they form a unique fingerprint.

Cite this