A study on the on-line measurement of transmission line impedances for improved relaying protection

I D Kim, R K Aggarwal

Research output: Contribution to journalArticle

30 Citations (Scopus)

Abstract

This paper proposed an on-line measurement of transmission line impedance in order to improve the accuracy of distance relays and analysis of power system. Distance relays are generally set by the estimated impedance of the protected lines, which involves a certain amount of error in itself. Especially, the zero sequence impedance has more erroneous terms associated with mutual effects in parallel line as well as uncertainty of ground return path. The proposed method is measuring impedance either during normal operation or during faults, and can be applied on-line correction of the setting value of distance relays. This on-line measured positive impedance may be used to monitor the transmission line condition during operation and more accurate impedance data may also improve performance of power system analysis. For verification of the proposed method, several simulations have been executed and shown satisfactory results. (C) 2006 Published by Elsevier Ltd.
LanguageEnglish
Pages359-366
Number of pages8
JournalInternational Journal of Electrical Power & Energy Systems
Volume28
Issue number6
DOIs
StatusPublished - 2006

Fingerprint

Electric lines
Systems analysis
Uncertainty

Cite this

@article{0ca8bbe576e24630963f83303160d8f5,
title = "A study on the on-line measurement of transmission line impedances for improved relaying protection",
abstract = "This paper proposed an on-line measurement of transmission line impedance in order to improve the accuracy of distance relays and analysis of power system. Distance relays are generally set by the estimated impedance of the protected lines, which involves a certain amount of error in itself. Especially, the zero sequence impedance has more erroneous terms associated with mutual effects in parallel line as well as uncertainty of ground return path. The proposed method is measuring impedance either during normal operation or during faults, and can be applied on-line correction of the setting value of distance relays. This on-line measured positive impedance may be used to monitor the transmission line condition during operation and more accurate impedance data may also improve performance of power system analysis. For verification of the proposed method, several simulations have been executed and shown satisfactory results. (C) 2006 Published by Elsevier Ltd.",
author = "Kim, {I D} and Aggarwal, {R K}",
note = "ID number: ISI:000238934500001",
year = "2006",
doi = "10.1016/j.ijepes.2006.01.002",
language = "English",
volume = "28",
pages = "359--366",
journal = "International Journal of Electrical Power & Energy Systems",
issn = "0142-0615",
publisher = "Elsevier",
number = "6",

}

TY - JOUR

T1 - A study on the on-line measurement of transmission line impedances for improved relaying protection

AU - Kim, I D

AU - Aggarwal, R K

N1 - ID number: ISI:000238934500001

PY - 2006

Y1 - 2006

N2 - This paper proposed an on-line measurement of transmission line impedance in order to improve the accuracy of distance relays and analysis of power system. Distance relays are generally set by the estimated impedance of the protected lines, which involves a certain amount of error in itself. Especially, the zero sequence impedance has more erroneous terms associated with mutual effects in parallel line as well as uncertainty of ground return path. The proposed method is measuring impedance either during normal operation or during faults, and can be applied on-line correction of the setting value of distance relays. This on-line measured positive impedance may be used to monitor the transmission line condition during operation and more accurate impedance data may also improve performance of power system analysis. For verification of the proposed method, several simulations have been executed and shown satisfactory results. (C) 2006 Published by Elsevier Ltd.

AB - This paper proposed an on-line measurement of transmission line impedance in order to improve the accuracy of distance relays and analysis of power system. Distance relays are generally set by the estimated impedance of the protected lines, which involves a certain amount of error in itself. Especially, the zero sequence impedance has more erroneous terms associated with mutual effects in parallel line as well as uncertainty of ground return path. The proposed method is measuring impedance either during normal operation or during faults, and can be applied on-line correction of the setting value of distance relays. This on-line measured positive impedance may be used to monitor the transmission line condition during operation and more accurate impedance data may also improve performance of power system analysis. For verification of the proposed method, several simulations have been executed and shown satisfactory results. (C) 2006 Published by Elsevier Ltd.

U2 - 10.1016/j.ijepes.2006.01.002

DO - 10.1016/j.ijepes.2006.01.002

M3 - Article

VL - 28

SP - 359

EP - 366

JO - International Journal of Electrical Power & Energy Systems

T2 - International Journal of Electrical Power & Energy Systems

JF - International Journal of Electrical Power & Energy Systems

SN - 0142-0615

IS - 6

ER -