Abstract
Component condition and substation (S/S) reliability have a material impact on the cost of customer interruptions in electricity distribution systems (DSs). However, these factors are not usually considered within distribution system reconfiguration (DSR) problem formulations, because of the lack of a readily available methodology. This paper presents such a method, making use of component condition scores which are now mandatory for distribution system operators (DSOs) in the UK. Based on these condition scores, condition-based failure rate can be calculated for each component. S/S reliability is a function of component condition, S/S configuration and the network upstream of the S/Ss. The reliability of the S/S then has an impact on the reliability indices of each load point (LP) it supplies. These factors are combined to deliver a better informed algorithm for DSR, which is verified through its application on two DSs. The annual savings, compared to the formulation that neglects component condition and S/S reliability, can be in the order of tens of thousands of U.S. dollars for a single DS.
Original language | English |
---|---|
Pages (from-to) | 122-138 |
Number of pages | 17 |
Journal | International Journal of Electrical Power and Energy Systems |
Volume | 109 |
Early online date | 13 Feb 2019 |
DOIs | |
Publication status | Published - 1 Jul 2019 |
Data Availability Statement
Data supporting this publication is openly available under an 'Open Data Commons Open Database License'. Additional metadata are available at: http://dx.doi.org/10.17634/154300-106 .Acknowledgements
The authors would like to thank four anonymous reviewers for their valuable comments, as well as Dr Graeme Coapes from Siemens plc, Hebburn for his helpful feedback.Keywords
- Component condition
- Condition-based failure rate
- Reconfiguration
- Reliability
- Substation